DISPELLING THERMAL COMFORT MYTHS, PART 1: Foundations For Applying ASHRAE Standard 55-2023
By Asit Kumar Mishra, Ph.D., Associate Member ASHRAE;
Robert Bean, Fellow/Life Member ASHRAE

Thermal comfort design is often plagued by certain myths and misconceptions that limit effective practice and implementation of existing standards. This leads to both energy waste and occupant dissatisfaction and the epicenter of thermostat wars. Thermal discomfort is a known deterrent to productivity and academic learning.This first part of a two-part column examines four common thermal comfort myths, provides evidence-based guidance for proper application of ASHRAE Standard 55-2023 and demonstrates how a holistic understanding of all thermal comfort parameters can improve design outcomes in architectural, enclosure, interior and HVAC systems. By dispelling these foundational myths, practitioners can create conditions for people to perceive thermal comfort and enable energy efficient environments and systems that are truly occupant centric, healthy and sustainable.
ASHRAE Standard 55-2023, Thermal Environmental Conditions for Human Occupancy,1 provides the foundation for thermal comfort conditions in buildings across multiple regions worldwide. However, widespread misconceptions about the standard and thermal comfort principles continue to limit its effective application. These myths range from oversimplified assumptions about temperature control to fundamental misunderstandings about the factors that influence human thermal perception.
The standard defines thermal comfort as “that condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation.” This seemingly simple definition 
encompasses a complex interplay of six key factors: four environmental parameters (air temperature [ta], mean radiant temperature [MRT], humidity [H] and air velocity [V ]) and two personal factors (clothing insulation [clo] and metabolic rate [met]).2 Additionally, under low met rates (<1.3) and clothing (<0.7), five local factors must also be assessed.1 Understanding the relationships of the 11 factors is crucial for effective design practice.
This first part of the column focuses on four foundational myths that constrain how practitioners think about comfort: conflating indoor air quality and thermal comfort, equating load calculations with comfort analysis, overreliance on thermostats and assuming a single temperature setpoint ensures comfort.
The Myths
Myth 1: Indoor Air Quality and Thermal Comfort are the Same Thing
Many practitioners incorrectly assume that indoor air quality (IAQ) and thermal comfort are related or even the same phenomenon, leading to confusion about which standards to apply and how to address occupant complaints.
Reality
Perception of IAQ and thermal comfort involve different physiological and neurological systems. IAQ primarily affects the respiratory system and involves chemical, biological and physical contaminants that can impact health. Thermal comfort, on the other hand, is a neurological response related to the body’s thermoregulatory system and heat exchange with the
environment. Figure 1 illustrates the six primary factors affecting occupant thermal sensation and perception.
ASHRAE explicitly separates these concerns in its standards structure:
• ANSI/ASHRAE Standard 62.1-2022, Ventilation and Acceptable Indoor Air Quality, and ANSI/ASHRAE Standard
62.2-2022, Ventilation and Acceptable Indoor Air Quality in Residential Buildings3,4 explicitly state they do not address
thermal comfort.
• ANSI/ASHRAE Standard 55-2023, Thermal Environmental Conditions for Human Occupancy, explicitly states it does not address indoor air quality. This separation exists because the solutions for IAQ problems (increased ventilation, particle and gas filtration, source control) are fundamentally different from thermal comfort solutions (modifications to
architectural, enclosure, interior systems; strategic selection in HVAC types; and incorporation of clothing and activity adjustments).
Practical Implications
• Address IAQ and thermal comfort as separate design challenges requiring different solutions.
• When using the term “comfort,” be specific. Is the reference to respiratory comfort or thermal comfort?
• Do not assume that solving one problem will solve the other.
•Use appropriate standards: ASHRAE Standards 62.1/62.2/241 for IAQ, ASHRAE Standard 55 for thermal comfort.
• Measure and monitor these parameters separately using appropriate sensors and assessment methods.
Myth 2: Load Calculations Equal Comfort Calculations
Perhaps the most prevalent misconception in HVAC practice is that load calculations serve as comfort calculations and that equipment sizing automatically ensures occupant comfort.
Reality
Load calculations determine equipment specifications and system capacity but do not assess human thermal sensation and perception. They focus on conductive heat gains and losses and effects from infiltration for regulation with air temperature control but ignore the comprehensive factors affecting perceptions of thermal comfort. None of these system engineering processes are required to ask, “what do people experience thermally based on what they are doing, what they are wearing or where they are positioned relative to the architecture and geometry of the occupied space?”
Comfort analysis requires evaluating all thermal comfort parameters simultaneously through tools like the predicted mean vote (PMV) model.2 A space might maintain 22°C (72°F) air temperature in compliance with building codes while contributing to the perception of discomfort due to the presence of (as examples) cold window surfaces, inadequate air movement or inappropriate humidity levels.5
Practical Implications
• Perform separate thermal comfort analysis using ASHRAE Standard 55 tools.
• Evaluate operative temperature (integrates MRT and tdb), humidity and air velocity around the occupant, not just air temperature as witnessed by a thermostat.
• Assess (when required) local discomfort factors (drafts, asymmetric radiation, floor temperatures, vertical temperature gradients).
Myth 3: Thermostats Control Thermal Comfort
Building operators and occupants often believe that adjusting thermostat settings directly controls thermal comfort and that the numerical value displayed represents the thermal experience of occupants.
The Reality
The numerical value on a thermostat does not represent thermal comfort. Thermostats monitor and control air
temperature at a single point, but thermal comfort per Standard 55-2023 depends on the complex interaction of up to all 11 factors, not just the air temperature at the location of the thermostat. The standard is also explicitly clear: where the person goes, so goes their thermal experience. Any sensor (e.g., thermostat or humidistat) that does not measure the conditions at the location of the occupant and across the occupant cannot stand as a proxy for Standard 55-2023.
More fundamentally, people sense (different from perception) heat rejection, retention and gain primarily through their skin, not the heat loss and gain in the space. Human thermal sensation is based on:
• Heat flux at the skin surface (the rate of heat transfer to/from the body);
• Local skin temperatures at various body parts; and
• Clothing and activity.
The body’s thermoregulation responds to personal factors while also being influenced by environmental conditions6 (Figure 1). This creates several critical limitations. Practitioners cannot ensure thermal comfort in a space. The experience of satisfaction or dissatisfaction is sensed by the body and perceived by the mind, thus the definition that thermal comfort is “a state of mind” not a state of the space. Practitioners cannot make an individual feel thermal comfort since thermal perception can vary widely across individuals. HVAC equipment enables the practitioner to move heat, moisture and air around; in and of themselves, these processes cannot be assumed to deliver conditions for thermal comfort.
Air-based HVAC systems control bulk air properties (temperature, absolute humidity, velocity) and radiant-based systems control surface temperatures affecting the mean radiant temperature, floor temperatures and radiant asymmetry. In conjunction with the architecture, enclosure and interior system, they also influence relative humidity, stratification,
general and ankle drafts. Collectively, systems cannot enforce personal choices in clothing and activity. That is, they cannot account for physiological differences between occupants or differences of personal preferences. This is why all factors must be considered.
Practical Implications
• Design architectural, enclosure, interior and HVAC systems to provide the thermal environmental conditions that support the perception of comfort, not to “deliver” comfort.
• Focus on controlling operative temperature rather than just air temperature.
• Provide occupant control, adaptive opportunities and mixed-mode systems wherever possible.
• Use proper thermal comfort analysis tools (PMV/PPD, adaptive comfort models) rather than relying on load calculations and HVAC design and air temperature setpoints.
• Consider personal comfort systems, adaptive opportunities and local environmental control to address individual differences.
• Monitor and validate thermal comfort through occupant feedback, not just temperature measurements.7
Myth 4: “A Single Temperature Setting Ensures Comfort”
Building codes and design practices often specify single air temperature setpoints (e.g., 70°F [21°C]) as if this alone determines thermal comfort.
The Reality
ASHRAE Standard 55 has never required specific setpoints including air temperatures. Instead, it defines acceptable ranges within combinations of all comfort parameters. Comfort zones defined using the standard are based on operative temperature (the combined effect of air temperature and mean radiant temperature), not air temperature alone.1 A setpoint, for example 70°F (21°C) air temperature, can contribute to perceptions of comfort or discomfort depending on the mean radiant temperature from surrounding surfaces, humidity levels, air movement and occupant clothing
and activity levels.
Practical Implications
• Focus on operative temperature ranges, not air temperature alone.
• Consider seasonal clothing adjustments when defining comfort zones.
• Use wider operative temperature bands when appropriate elevated air movement is available.
• Evaluate comfort zones dynamically based on actual occupancy patterns.
• If doing research that references thermal comfort, do not use air temperature data from a thermostat as representative data for thermal comfort. There is no statement in Standard 55-2023 that supports this position.
Discussion and Interim Conclusions
These four foundational myths highlight the critical need for practitioners to separate indoor air quality from thermal comfort, distinguish equipment sizing from comfort analysis, move beyond thermostat numbers and abandon the notion that a single temperature setpoint guarantees satisfaction. Success in thermal comfort design requires moving beyond simple air temperature centric thinking to understanding how all six primary parameters and local factors interact for real occupants in real spaces.
By addressing these myths, practitioners can begin to:
• Frame comfort explicitly as a human state of mind, not a property of air or equipment;
• Use ASHRAE Standard 55 as a comfort standard, not a load or control standard; and
• Design and commission systems around operative temperature and all relevant parameters at the occupant location.
Part 2 will build on this foundation by examining four additional myths related to air movement, humidity, perceived gender bias and the use of the PMV model in practice as well as by exploring local discomfort, adaptive comfort and energy and sustainability implications in more detail.
References
1. ANSI/ASHRAE Standard 55-2023, Thermal Environmental Conditions for Human Occupancy.
2. Fanger, P.O. 1972. Thermal Comfort, Analysis and Applications in Environmental Engineering. New York: McGraw Hill.
3. ANSI/ASHRAE Standard 62.1-2022, Ventilation and Acceptable Indoor Air Quality.
4. ANSI/ASHRAE Standard 62.2-2022. Ventilation and Acceptable Indoor Air Quality in Residential Buildings.
5. Bean, R., R. Mora. 2018. “Prioritizing thermal comfort for homes: A case study in using Standard 55 for a residential
building.” ASHRAE Journal 60(9):28 – 37, 2018.
6. 2021 ASHRAE Handbook—Fundamentals.
7. Mishra, A., M. Ramgopal, 2013. “Field studies on human thermal comfort: An overview.” Build. Environ. 64:94 – 106. https://doi.org/10.1016/j.buildenv.2013.02.015
Published MAY 2026 ashrae.org ASHRAE JOURNAL, download here
Asit Kumar Mishra, Ph.D., is research fellow, University College Cork, Cork, Ireland.
Robert Bean, RET, P.L..(Eng.) is a retired practitioner from Alberta, Canada.